Gas Combustible gases (consult manufacture) | Temperature Range -40 to +140°F (-40 to +60°C) |
Ranges 0 to 100% LEL | Humidity Range 15 to 96% rh |
Gas supply Diffusion | Pressure Range 700 to 1,300 hPa |
Response Time T90 less than 8 seconds (depending on gas) | Signal Connection to Controller 3 shielded wire x 18 AWG less than 1000 feet |
Expected Sensor Life Approximately 5 years |
CC 0238EX | CC 24UL |
Output Signal 0.2 to 1 mA | Output Signal 0.2 to 1 mA or 4 to 20 mA |
Power Supply 15 to 30 V, 100 mA | Power Supply 18 to 24 V (maximum 26 V), 300 mA |
Housing Aluminum explosion proof Stainless steel sensor housing | Housing Aluminum explosion proof Stainless steel sensor housing |
Weight 21 ounces (600 grams) | Weight 3.5 pounds (1587 grams) |
Dimensions 4x4.4x2.2 inches (100x110x55 mm) (HxWxD) | Dimensions 4.9x4.5x3.7 inches (125x115x95 mm) (HxWxD) |
Ex-Approvals EX e s 3n G5 | Housing Approvals Class 1, Groups, B, C, D UL FM EEx d IIC Type 4X (IP 64) |