Gases Depending on transmitter: Combustible / explosive Toxic gases and vapors Oxygen | Alarms 3 alarm points Freely adjustable within the detection range |
Detection Range Depending on requirements: % LEL, volume %, ppm, mg/m3 | Relay Outputs 4 voltage-free relays for alarm and fault Normally closed contact (NC) Normally open contact (NO) |
Temperature Range 32 to +131°F (0 to +55°C) | Display 3-digit LED display 1 LED green – operational status 1 LED yellow – fault 3 LEDs red – alarm Display of maximum / minimum values |
Response Time T90 less than 3 seconds |
Power Source 24 VDC | Function Keys Push-button operation for all functions, like alarm points, calibration, function test, and relay test |
Power Consumption Maximum 150 mA at 24 V DC | Models GMA 41B / GMA 44B Power supply 24 V with bus-system |
Input Signal 0.2 to 1 mA or 4 to 20 mA | Key-Operated Switch GMA 41 / GMA 44 SW (24 V) |
Output Signal Linear 4 to 20 mA (GMA 41) | Power Supply Module Available on request |
Alarm Functions Exceeding / desending Latching / non-latching Re-settable / non-resettable Hysteresis adjustable Delay-time 0 to 2 minutes Alarm thresholds completely adjustable | Dimensions 3.6x4.24x2.32 inches (90x106x58 mm) (HxWxD |